| A standard boiler system works on a short, sharp | | | | stage, it is also worth looking at practical issues to |
| shock premise with an instant response to the call | | | | see if heat pump technology will be suitable, as |
| for heat. A heat pump - whether air source or | | | | there are particular installation requirements. For |
| ground source - delivers a constant flow of heat. | | | | example, an area approximately two and a half |
| The efficiency comparison is rather like driving a | | | | times the size of the property is needed to lay |
| car stop/start through town as opposed to a | | | | the ground loops for a GSHP. An ASHP requires |
| smooth, even cruise at one speed. | | | | space outside, pipework and wiring from the |
| Conventional boilers produce hot water at a | | | | external unit back into the property and both |
| temperature in excess of 65°C compared | | | | types require a plant or utility room to house the |
| with 35 - 45°C from a heat pump. These | | | | equipment. |
| lower temperatures will adversely affect the | | | | Installer Perspective |
| performance of underfloor heating (UFH) if they | | | | Dominic Taylor-Lane of Purus Navitas, an |
| are not factored in prior to installation. | | | | experienced installer of underfloor heating and |
| Significant Factors | | | | heat pumps recently worked on a refurbishment |
| The first consideration is the amount of pipe in | | | | project where the householders decided to install |
| the floor and the spacing required. A greater | | | | a conventional boiler with a view to changing to a |
| amount of pipe may be required for use with a | | | | ground source heat pump in the future. |
| heat pump due to the lower water temperature. | | | | Dominic explains how the system was |
| Tube spacing for a conventional boiler might | | | | future-proofed in this instance. 'The owners have |
| typically be at 200mm centres and a heat pump | | | | the space for boreholes so, although a |
| at 150mm centres. However, there are so many | | | | conventional boiler has been installed, the ground |
| variables that this can only be determined when | | | | source heat pump is an option for later. For this |
| the design has taken into account such factors as | | | | reason the plant room was purpose-built to be |
| room size, glazing and floor covering. | | | | large enough to house a ground source heat |
| It is important to establish what floor covering will | | | | pump and buffer cylinder. Pre-insulated pipe was |
| be used when the pump is installed. Many floor | | | | run into the plant room terminating in a manhole |
| coverings including most tiles, slate, laminates and | | | | cover close to the proposed borehole site to |
| solid wood work well with UFH. Carpet and | | | | minimise any future disturbance to the work |
| underlay are acceptable as long as a tog of more | | | | already done.' |
| than 2.5 is not used. | | | | Of insulation requirements Dominic comments 'The |
| For any underfloor heating installation, levels of | | | | internal walls were lagged during the refurbishment |
| insulation are essential to the efficiency of the | | | | so in this instance the underfloor heating pipe |
| system, but when a heat pump is to be used this | | | | spacing specifications made by Nu-Heat were |
| is even more critical. Insulation levels should ideally | | | | similar to a normal specification. The first floor |
| ensure that less than 45 watts of heating are | | | | radiators run off a different circuit, but we |
| required per square metre of floor space. | | | | installed oversized aluminium radiators so they will |
| If the future heat pump system is to include | | | | work with a heat pump in future.' |
| radiators, these must be sized correctly so that | | | | As increasing numbers of customers think about |
| they continue to work efficiently after the | | | | their long-term energy needs, future-proofing is a |
| changeover. As a rule of thumb, radiators will | | | | serious matter. Ultimately, as long as the initial |
| need to be around one third bigger than when | | | | design and installation of UFH has taken into |
| used with a conventional boiler. The alternative is | | | | consideration future integration with a heat pump, |
| high efficiency radiators that should be sized | | | | the final system will run efficiently and is likely to |
| according to manufacturer specification. | | | | last for a long time to come. |
| Along with the future proofing required at design | | | | |